NCC check - Riverside House - Stage 2

Generated from the demo on 30 August 2026 · Run 3 · 12 rule packs
Which packsAS 1657 - fixed platforms, walkways and stairways (starter pack), Livable Housing Design - Silver level (starter pack), ABCB Housing Provisions 2022 - NSW variations, ABCB Housing Provisions 2022 - NT variations, ABCB Housing Provisions 2022 - QLD variations, ABCB Housing Provisions 2022 - SA variations, ABCB Housing Provisions 2022 - TAS variations, ABCB Housing Provisions 2022 - WA variations, ABCB Housing Provisions 2022, NCC 2022 Performance Requirements - TAS variations, NCC 2022 Performance Requirements - VIC variations, NCC 2022 Performance Requirements
This is a sample report from the Plumbline demo. The layout, sections and wording are exactly what the add-in writes out of Revit. The findings are sample data - they do not describe a real building.
12 of 12 rule packs are unverified. Thresholds and clause references in them have not been confirmed against the NCC edition in force, and no state or territory variations have been applied. Every finding from them is a prompt to check, not a result.
Which packsAS 1657 - fixed platforms, walkways and stairways (starter pack); Livable Housing Design - Silver level (starter pack); ABCB Housing Provisions 2022 - NSW variations; ABCB Housing Provisions 2022 - NT variations; ABCB Housing Provisions 2022 - QLD variations; ABCB Housing Provisions 2022 - SA variations; ABCB Housing Provisions 2022 - TAS variations; ABCB Housing Provisions 2022 - WA variations; ABCB Housing Provisions 2022; NCC 2022 Performance Requirements - TAS variations; NCC 2022 Performance Requirements - VIC variations; NCC 2022 Performance Requirements

Summary

11Fail
15To confirm
17Pass
1Set aside
6 closed since the last run 1 reopened 2 new 1 element deleted
Failures by levelCount
Level 19
Ground2
Failures by clauseCount
Livable Housing Design - doorways (verify)2
ABCB Housing Provisions 2022 NT 13.5.2(1), NT Table 13.5.22
NCC 2022 ABCB Housing Provisions 10.3.1(1)(a)2
AS 1657 - guardrailing (verify)1
Livable Housing Design / AS 1428.1 - ramps (verify)1
NCC 2022 ABCB Housing Provisions 10.3.1(1)(b)1
NCC 2022 ABCB Housing Provisions 10.3.1(1)(c)1
NCC 2022 ABCB Housing Provisions 10.3.1(1)(d)1

Failures - 11, worst first

SeverityClauseRequirementElement LevelObservedRequiredNote
CRITICAL - 2
Critical Livable Housing Design / AS 1428.1 - ramps (verify)Flags ramps steeper than the configured maximum gradient of 1:14. Entry ramp #700006 Ground1:11≤ 1:14 Reads the ramp's own gradient. It does not check landings, handrails or the total rise across a series of ramps.
Critical AS 1657 - guardrailing (verify)Flags plant and walkway guardrails whose readable height is below the configured minimum of 900 mm. Balustrade - stair #700003 Level 1840 mm≥ 900 mm Reads the railing type's height parameter. It says nothing about openings between rails, or whether a guardrail exists where one is required but none is modelled.
MAJOR - 9
Major Livable Housing Design - doorways (verify)Flags doorways whose estimated clear opening width is below the configured minimum of 820 mm. Door 870 × 2100 #700005 Ground≈ 815 mm clear≥ 820 mm clear Measured from the door's width parameter less any deduction the rule sets, which approximates clear opening width rather than measuring it. A marginal result needs checking on the drawing.
Major Livable Housing Design - doorways (verify)Flags doorways whose estimated clear opening width is below the configured minimum of 820 mm. Door 820 × 2100 #700004 Level 1≈ 765 mm clear≥ 820 mm clear Measured from the door's width parameter less any deduction the rule sets, which approximates clear opening width rather than measuring it. A marginal result needs checking on the drawing.
Major NCC 2022 ABCB Housing Provisions 10.3.1(1)(a)Flags habitable rooms (excluding kitchens) whose ceiling height is below 2400 mm. Bed 2 #700015 Level 12 340 mm≥ 2 400 mm Applies to flat-ceiling condition only; rooms with a sloping ceiling or ceiling projections are governed by 10.3.1(1)(e) instead and are not covered by this rule.
Major NCC 2022 ABCB Housing Provisions 10.3.1(1)(a)Flags habitable rooms (excluding kitchens) whose ceiling height is below 2400 mm. Ensuite #700016 Level 12 060 mm≥ 2 400 mm Applies to flat-ceiling condition only; rooms with a sloping ceiling or ceiling projections are governed by 10.3.1(1)(e) instead and are not covered by this rule.
Major NCC 2022 ABCB Housing Provisions 10.3.1(1)(b)Flags kitchens whose ceiling height is below 2100 mm. Ensuite #700018 Level 12 060 mm≥ 2 100 mm Flat-ceiling condition only; a sloping-ceiling kitchen is not addressed by this rule.
Major NCC 2022 ABCB Housing Provisions 10.3.1(1)(c)Flags corridors and passageways whose ceiling height is below 2100 mm. Ensuite #700021 Level 12 060 mm≥ 2 100 mm Flat-ceiling condition only.
Major NCC 2022 ABCB Housing Provisions 10.3.1(1)(d)Flags bathrooms, shower rooms, laundries, sanitary compartments, airlocks, pantries, storerooms, garages and car parking areas whose ceiling height is below 2100 mm. Ensuite #700025 Level 12 060 mm≥ 2 100 mm Flat-ceiling condition only; room-name matching cannot distinguish an airlock or storeroom from similarly-named non-habitable spaces the clause does not intend to cover.
Major ABCB Housing Provisions 2022 NT 13.5.2(1), NT Table 13.5.2Flags habitable rooms in a climate zone 1 project whose total ventilation opening area, as a fraction of floor area, is below the minimum for a room without a ceiling fan or evaporative cooler. Bed 3 #700008 Level 13.1% of floor area≥ 5% of floor area Assumes 50% of window glazed area is openable, since the model does not record actual window hardware; treat a Fail as needing verification against the window schedule. This threshold applies only where no ceiling fan or evaporative cooler serves the room and the project is in climate zone 1 - lower thresholds apply where a fan or cooler is fitted, which this check cannot detect. Also does not evaluate the alternative compliance path of ventilating via an adjoining room's opening.
Major ABCB Housing Provisions 2022 NT 13.5.2(1), NT Table 13.5.2Flags habitable rooms in a climate zone 3 project whose total ventilation opening area, as a fraction of floor area, is below the minimum for a room without a ceiling fan or evaporative cooler. Bed 3 #700010 Level 13.1% of floor area≥ 5% of floor area Assumes 50% of window glazed area is openable. Applies only where no ceiling fan or evaporative cooler serves the room and the project is in climate zone 3 - lower thresholds apply otherwise, which this check cannot detect. Does not evaluate the adjoining-room ventilation path.

To confirm - 15

The model could not decide these. Most of the Code is about materials, ratings, certification and procedure that no geometry carries, so each one names what would settle it. They are work for a person, not defects.

AreaClauseRequirementElement LevelObservedRequiredWhat would settle it
acoustics NCC 2022 Vol One Part F7 / Housing Provisions Part 10.7Raises sound insulation as a single item to confirm. Whole building #700032 - needs confirmation - Confirm there is test evidence or an acoustic assessment for every wall and floor separating sole-occupancy units. Ratings come from tested assemblies where material, thickness and insulation act together, so a wall's modelled thickness cannot show compliance.
energy NCC 2022 Vol One Section J / Housing Provisions Section 13Raises the building's energy efficiency obligation as a single item to confirm. Whole building #700029 - needs confirmation - Confirm which compliance pathway this project uses - a NatHERS certificate, a JV3 or whole-of-home assessment, or the elemental provisions - and that it covers the design as currently modelled. Note that some inputs to it are specification decisions rather than assessment outputs: roof and wall solar absorptance comes from the finish selected and its data sheet, and it changes which insulation R-Value the tables require.
fire-resistance NCC 2022 Vol One Sections C and SpecificationsRaises fire-resisting construction as a single item to confirm. Whole building #700030 - needs confirmation - Confirm the type of construction, and that every element required to have a fire resistance level has evidence of one. An FRL is a property of a tested system, so nothing in the model can show it.
fire-services NCC 2022 Vol One Part E1Raises fire fighting services as a single item to confirm. Whole building #700031 - needs confirmation - Confirm that sprinklers, hydrants, hose reels and extinguishers are provided where required, against the fire services design. These are usually in a linked services model, so their absence here does not mean they are absent from the building.
structure NCC 2022 Vol One Section B / Housing Provisions Sections 2 to 6Raises structural adequacy as a single item to confirm. Whole building #700033 - needs confirmation - Confirm the structural design and certification cover the building as modelled, including footings sized for the site classification and framing for the wind classification. Structural adequacy needs loads and materials, not shapes.
waterproofing NCC 2022 ABCB Housing Provisions 10.2.2Raises NCC 2022 ABCB Housing Provisions 10.2.2 as an item to confirm, because the model cannot decide it. Whole building #700039 - needs confirmation - Check the shower waterproofing detail and specification against Figure 10.2.2 to confirm floor, wall, junction and penetration treatment matches the shower type modelled (enclosed, unenclosed or preformed base).
waterproofing NCC 2022 ABCB Housing Provisions 10.2.3Raises NCC 2022 ABCB Housing Provisions 10.2.3 as an item to confirm, because the model cannot decide it. Whole building #700040 - needs confirmation - Check the wet area detail drawings and waterproofing specification for the area outside the shower to confirm floor and wall/floor junction treatment matches the flooring material used.
waterproofing NCC 2022 ABCB Housing Provisions 10.2.4Raises NCC 2022 ABCB Housing Provisions 10.2.4 as an item to confirm, because the model cannot decide it. Whole building #700041 - needs confirmation - Check the wet area detail drawings and waterproofing specification for the bath or spa recess to confirm floor, wall and junction treatment matches the vessel type (freestanding, non-freestanding or inserted) shown in Figure 10.2.4a/10.2.4b.
waterproofing NCC 2022 ABCB Housing Provisions 10.2.5Raises NCC 2022 ABCB Housing Provisions 10.2.5 as an item to confirm, because the model cannot decide it. Whole building #700042 - needs confirmation - Check the wet area detail drawings and waterproofing specification to confirm wall, floor and junction treatment around each vessel, and in laundries, WCs and WCs fitted with a handheld bidet spray, matches Figure 10.2.5 and the extents set for each case.
waterproofing NCC 2022 ABCB Housing Provisions 10.2.6Raises NCC 2022 ABCB Housing Provisions 10.2.6 as an item to confirm, because the model cannot decide it. Whole building #700043 - needs confirmation - Check the waterproofing specification to confirm the nominated waterproofing system is documented against either the waterproof materials in 10.2.8, or the water resistant substrate and surface materials in 10.2.9 and 10.2.10.
waterproofing NCC 2022 ABCB Housing Provisions 10.2.7Raises NCC 2022 ABCB Housing Provisions 10.2.7 as an item to confirm, because the model cannot decide it. Whole building #700044 - needs confirmation - Check the waterproofing specification to confirm every wet-area material is listed against the waterproof materials in 10.2.8 or the water resistant materials in 10.2.9.
waterproofing NCC 2022 ABCB Housing Provisions SA 10.2.1Raises NCC 2022 ABCB Housing Provisions SA 10.2.1 as an item to confirm, because the model cannot decide it. Whole building #700036 - needs confirmation - Check the wet area detail drawings and waterproofing specification to confirm treatment around washing machine tap outlets, inset kitchen or bar vessels, and floor wastes matches SA Figures 10.2.1a to 10.2.1c and AS 3740.
waterproofing NCC 2022 Vol One Part F2 / Housing Provisions Part 10.2Raises wet area waterproofing as a single item to confirm. Whole building #700034 - needs confirmation - Confirm the wet area details show membranes, falls and junctions to the required extents. These are finishes and detailing, which a model does not carry as measurable elements.
weatherproofing NCC 2022 Vol Two NSW 4.2.8Raises one item asking whether the slab-on-ground damp-proofing membrane meets the specified material (thickness, impact resistance, branding) and installation detail (laps, service-penetration sealing, puncture repair). Whole building #700035 - needs confirmation - Confirm against the slab damp-proofing membrane specification and the slab pour inspection/hold-point record.
weatherproofing NCC 2022 Vol Two SA 4.2.8Raises one item asking whether the slab-on-ground damp-proofing membrane meets the specified material (thickness, impact resistance, branding) and installation detail (laps, service-penetration sealing, puncture repair). Whole building #700037 - needs confirmation - Confirm against the slab damp-proofing membrane specification and the slab pour inspection/hold-point record.

What was done - 2 changes

Every change the tool made or was told about, with the value it replaced and who was at the keyboard. The same record is written into the Revit file, so it travels with the model.

WhenRunByOutcomeClause ElementLevelWasRequiredDetail
2026-08-28 09:44:001 j.marksSet asideNCC 2022 ABCB Housing Provisions 10.2.1 Whole building - needs confirmation - Covered by a consultant’s report.
2026-08-28 09:41:001 j.marksFixed by toolLivable Housing Design - doorways (verify) Door 820 × 2100 #700051 Ground≈ 780 mm clear ≥ 820 mm clearWidth 870 → 920 mm. Type parameter; 4 instances moved with it.

Set aside - 1

Judged not to apply to this project. Kept in the report with the reason given, because a decision nobody can see is not a decision anyone can review.

ClauseRequirementElementLevel Reason givenWhen
NCC 2022 ABCB Housing Provisions 10.2.1Raises NCC 2022 ABCB Housing Provisions 10.2.1 as an item to confirm, because the model cannot decide it. Whole building #700038 - Covered by a consultant’s report28 Aug 2026

Passes - 17

Show what passed
ClauseRequirementElementLevel ObservedRequired
ABCB Housing Provisions 2022 NT 13.5.2(1), NT Table 13.5.2Flags habitable rooms in a climate zone 1 project whose total ventilation opening area, as a fraction of floor area, is below the minimum for a room without a ceiling fan or evaporative cooler. Living #700009Ground 6.8% of floor area≥ 5% of floor area
ABCB Housing Provisions 2022 NT 13.5.2(1), NT Table 13.5.2Flags habitable rooms in a climate zone 3 project whose total ventilation opening area, as a fraction of floor area, is below the minimum for a room without a ceiling fan or evaporative cooler. Living #700011Ground 6.8% of floor area≥ 5% of floor area
AS 1657 - guardrailing (verify)Flags plant and walkway guardrails whose readable height is below the configured minimum of 900 mm. Balustrade - deck #700002Ground 1 010 mm≥ 900 mm
AS 1657 - stairway geometry (verify)Flags plant and service stairs whose riser or going falls outside the configured ranges. Main stair #700001Ground riser 195, going 240riser 115–190, going 240–355
NCC 2022 ABCB Housing Provisions 10.2.14(a)Flags shower areas that contain no floor waste / floor drain fixture. Whole building #700014 - 1 found≥ 1
NCC 2022 ABCB Housing Provisions 10.3.1(1)(b)Flags kitchens whose ceiling height is below 2100 mm. Bed 2 #700017Level 1 2 340 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(b)Flags kitchens whose ceiling height is below 2100 mm. Kitchen #700019Ground 2 550 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(c)Flags corridors and passageways whose ceiling height is below 2100 mm. Bed 2 #700020Level 1 2 340 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(c)Flags corridors and passageways whose ceiling height is below 2100 mm. Kitchen #700022Ground 2 550 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(c)Flags corridors and passageways whose ceiling height is below 2100 mm. Living #700023Ground 2 490 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(d)Flags bathrooms, shower rooms, laundries, sanitary compartments, airlocks, pantries, storerooms, garages and car parking areas whose ceiling height is below 2100 mm. Bed 2 #700024Level 1 2 340 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(d)Flags bathrooms, shower rooms, laundries, sanitary compartments, airlocks, pantries, storerooms, garages and car parking areas whose ceiling height is below 2100 mm. Kitchen #700026Ground 2 550 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(d)Flags bathrooms, shower rooms, laundries, sanitary compartments, airlocks, pantries, storerooms, garages and car parking areas whose ceiling height is below 2100 mm. Living #700027Ground 2 490 mm≥ 2 100 mm
NCC 2022 ABCB Housing Provisions 10.3.1(1)(d)Flags bathrooms, shower rooms, laundries, sanitary compartments, airlocks, pantries, storerooms, garages and car parking areas whose ceiling height is below 2100 mm. Garage #700028Ground 2 400 mm≥ 2 100 mm
NCC 2022 Vol Two NSW 9.4.3(1)(b)Flags a wall between a garage top dwelling and a non-associated private garage below, thinner than 90 mm. Cavity wall - external #700007Ground 110 mm leaf≥ 90 mm
NCC 2022 Vol Two SA 9.2.1(a)Flags a Class 1 exterior wall set back less than 900 mm from an allotment boundary, other than a boundary to a road or public space. External walls #700012 - 1 240 mm min≥ 900 mm
NCC 2022 Vol Two SA 9.2.8(a)(ii)Flags a Class 1 dwelling exterior wall within 2 m of the allotment boundary that would need to be fire-resisting to the underside of the roof covering or ceiling lining under this carport-exemption alternative. External walls #700013 - 1 240 mm min≥ 900 mm